SU120C-38042

Safety isolating transformers

SU120C-38042
CLI safeiso ce

Application

Open single-phase safety isolating transformer designed and tested according to norm EN61558-2-6. Separate insulated windings and protected against dust, humidity and corrosion through complete impregnation in heat tempered varnish. For fixed installation in cabinets or switchboards. The transformer is designed according to DnV, Lloyds register of shipping and Bureau Veritas standards witch require 45°C ambient temperature. Industrial transformer designed for low voltage installation in processing industry and switchboards, class I. The transformer has to be mounted in cover. Uncovered installation prohibited. Special designed metal plate covers available (Type SUK). The transformer must be protected against short circuit and overload with separate fuse arrangement.

 

Technical Specifications
SU120C-38042
1
47 - 63 Hz
380 - 400 - 440 - 450 - 480 V
42 V
11,9 A
500 VA
IP00
Dimensions
120 mm
117 mm
120 mm
6,6 kg
Ordering Information
3-060-000001
5703451010462

downloads

 SU

dimension drawings

No dimension drawings available

wiring diagram

No wiring diagram available

Products in this category
Type Article No Power Secondary Current Weight IP stock
SU120C-38042 3-060-000001 500 VA 11,9 A 6,6 kg IP00
SU150C-38042 3-060-000002 1000 VA 23,8 A 13,3 kg IP00